Scope of delivery
Detector and dust cap
Application
Suitable in areas, in which temporary high variations in temperature arise.
Where high dirt and heat fluctuation which can the impact of conventional alarm units to impair.
Addressable applicable.
Function
Equipped with one heat sensor.
Measures permanent the ambient temperature, with exceeding of the maximum temperature, the detector
sends a danger signal to control panel, at short term exceeding no alarming takes place.
Built in short circuit isolator
|
Communication protocol |
C-NET |
|
Operating voltage (modulated) |
12... 33 VDC |
|
Operating current (quiescent) |
~200 μA |
|
Ext. alarm indicator |
2 |
|
Operating temperature |
-10... +50 °C |
|
Storage temperature |
-30... +70 °C |
|
Humidity |
≤95 % rel. |
|
Color |
white, ~RAL 9010 |
|
Protection category EN60529/IEC529 |
IP40 |
|
– with detector base seal RS720 |
IP42 |
|
System compatibility |
C-NET - Cerberus Pro |
|
Standards |
EN54-5 / EN54-17 |
|
Dimensions |
(detector with base) Ø117 x 59 mm |
|
Approvals |
Activefire - AFP- 2469 VdS G209065 |
DB721 Detector base with loop contactFor all point detectors of the series Cerberus PRO FD720.
DBS720 Sounder baseCompatible to all FD720 point detectors. For surface supply line until cable 8 mm in diameter.
RS720 Detector base sealFor higher protection category.
FDBZ291 Designation plateTo identify the location address.
LP720 Detector Locking deviceFor locking the detector to the base.