Scope of delivery
Application
Function
|
Communication protocol |
C-NET, collective, or conventional |
|
Operating voltage (modulated) |
12... 33 VDC |
|
Operating current (quiescent) |
~170... ~230 μA |
|
Ext. alarm indicators that can be connected |
2 |
|
Permissible air speed |
max. 5 m/s |
|
Operating temperature |
-10... +50 °C |
|
Storage temperature |
-30... +70 °C |
|
Humidity |
≤95 % rel. |
|
Color |
white, ~RAL 9010 |
|
Protection category EN60529/IEC529 |
IP40 |
|
– with detector base seal RS720 |
IP42 |
|
System compatibility |
C-NET FS720 |
|
Standards |
EN54-7 / EN54-17 |
|
Dimensions |
(detector with base) Ø117 x 56 mm |
|
Approvals |
Activfire - AFP 2799 VdS G211070 |
DB721 Detector base with loop contactFor all point detectors of the series Cerberus PRO FD720.
RS720 Detector base sealFor higher protection category.
DBS720 Sounder baseCompatible to all FD720 point detectors. For surface supply line until cable 8 mm in diameter.
FDBZ291 Designation plateTo identify the location address.